ABB ACH550-UH User Manual page 416

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

2-70
Code
Name
1615
SAVE
PARAM
1616
DISP ALRMS
1617
DRIVE TEST
1618
PASS CODE
1619
PAR LOCK
1620
RUN EN TXT
1621
ST EN1 TXT
1622
ST EN2 TXT
1623
ST EN3 TXT
Parameters
Group 16: System Control
Resolution
Range
1
0 = DONE
1 = SAVE
1
0 = DISABLE
1 = ENABLE
1
0 = DISABLE
1 = ENABLE
1
0 - 65535
1
0 = LOCKED
1 = OPEN
1
0 = RUN ENABLE
1 = DAMPER END SWTCH
2 = VALVE OPENING
3 = PRE-LUBE CYCLE
1
0 = START ENABLE 1
1 = VIBRATION SWITCH
2 = FIRESTAT
3 = FREEZESTAT
4 = OVERPRESSURE
5 = VIBRATION TRIP
6 = SMOKE ALARM
7 = SAFETY OPEN
8 = LOW SUCTION
1
0 = START ENABLE 2
...
1
0 = START ENABLE 3
...
ACH550 E-Clipse Bypass User's Manual
Default
Description
0
Save User Settings (SaveImm +
SavePwrd).
ENABLE
Enables alarms to be displayed:
(1)
INP PHASE A LOSS,
INP PHASE B LOSS,
INP PHASE C LOSS,
MTR OVERLOAD,
BYPASS DISABLED,
DRIVE SETUP,
PCB TEMP
DRIVE LINK ERROR
DRIVE FAULTED
DISABLE
Enables drive test mode. Drive
(0)
contactor is opened.
0
Enter correct password to here in
order to change value of the PAR
LOCK. Default password value is
"123".
OPEN
When switched to "LOCKED"
(1)
prevents parameter changes
from panel. Does not affect to
Field Bus writes, expect
changing the lock value itself:
correct password must always be
set first, even in case of Field
Bus.
RUN
Alternative text choices for alarm
ENABLE
4006.
(0)
START
Alternative text choices for alarm
ENABLE
4021.
1
(0)
START
Alternative text choices for alarm
ENABLE
4022.
2
See parameter 1621 for range.
(0)
START
Alternative text choices for alarm
ENABLE
4023.
3
See parameter 1621 for range.
(0)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents