1-12
Motor compatibility
The motor, drive, and supply power must be compatible:
Specification
Motor type
Nominal current
Nominal frequency
Voltage range
Insulation
Tools required
To install the ACH550 you need the following:
• Screwdrivers (as appropriate for the mounting hardware used)
• Wire stripper
• Tape measure
• Drill
• Frame sizes R5...R8 with UL type 12 enclosure: Punch for conduit mounting
holes
• Frame sizes R7/R8: pallet truck and hoist
• For installations involving frame size R6...R8: The appropriate crimping tool for
power cable lugs. See
• Mounting hardware: screws or nuts and bolts, four each. The type of hardware
depends on the mounting surface and the frame size:
Frame Size
R1...R4
R5
R6
R7...R8
• For installations involving frame size R7...R8: Hoist.
Installation
Motor
Verify
3-phase induction motor
Motor value is within this
range: 0.15...1.5 * I
(I
= normal use current)
2N
10...500 Hz
Motor is compatible with
the ACH550 voltage range.
500...600 V drives: Either
the motor complies with
NEMA MG1 Part 31, or a
du/dt filter is used between
the motor and drive.
Power terminal considerations – R6 Frame
Mounting Hardware
M5
#10
M6
1/4 in
M8
5/16 in
M10
7/16
• Type code label on drive, entry for Output I
or
2N
• Type code on drive and rating table in
Technical data
208...240 V (for ACH550-xx-xxxx-2) or
380...480 V (for ACH550-xx-xxxx-4)
500...600 V (for ACH550-xx-xxxx-6)
For ACH550-xx-xxxx-6
Secures free standing cabinets if required.