ACH550-UH User's Manual
Code
5309
5310
5311
5314
5315
5316
Description
EFB STATUS
EFB PAR10
EFB PAR11
EFB PAR14
EFB PAR15
EFB PAR 16
EFB Protocol Reference
Modbus
N2
FLN
This parameter indicates the internal status of the EFB
Protocol as follows:
• IDLE – EFB Protocol is configured but not receiving
messages.
• TIMEOUT – Time between valid messages has
exceeded the interval set by parameter 3019.
• OFFLINE – EFB Protocol is receiving messages NOT
addressed to this drive.
• ONLINE – EFB Protocol is receiving messages
addressed to this drive.
• RESET – EFB Protocol is in reset.
• LISTEN ONLY – EFB Protocol is in listen-only mode.
Not used
Sets the response turnaround time in
for Comm
milliseconds in addition to any fixed delay
setup.
imposed by the protocol. When this protocol is
selected, the default value is:
3 ms
0 ms
Not used for Comm setup.
Not used for Comm setup.
Not used for Comm setup.
Not used for Comm setup.
1-191
BACnet
5 ms
This parameter, together
with parameter 5317,
EFB
17, sets BACnet
PAR
Device Object Instance
IDs:
• For the range 1 to
65,535: This
parameter sets the ID
directly (5317 must be
0). For example, the
following values set
the ID to 49134: 5311
= 49134 and 5317 = 0.
• For IDs > 65,335: The
ID equals 5311's value
plus 10,000 times
5317's value. For
example, the following
values set the ID to
71234: 5311 = 1234
and 5317 = 7.
This parameter indicates
the count of MS/TP tokens
passed to this drive.
Embedded fieldbus