ABB ACH550-UH User Manual page 492

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

2-146
{52}
{53}
{59}
{68}
{70}
{71}
{72}
{73}
{74}
{75}
{76}
{77}
{78}
{79}
{80}
86
88
89
90
93
Embedded fieldbus
FLN Detailed Point Descriptions
Point
START ENA 3
This point is commanded by FLN to assert the system Start
Enable 1 command (1 = ENABLE, 0 = DISABL). Bypass
parameter 1605 must be set to COMM for FLN to have this
control.
START ENA 4
This point is commanded by FLN to assert the system Start
Enable 1 command (1 = ENABLE, 0 = DISABL). Bypass
parameter 1606 must be set to COMM for FLN to have this
control.
PAR LOCK
When switched to locked prevents parameter changes from
the panel.
FLN LOC CTL
Commands the bypass into FLN Local Control. In this
mode, FLN takes the bypass control from the normal
source. However, the panel's HAND mode still has priority.
DI 1 ACTUAL
This point indicates the status of bypass Digital Input 1
(1 = ON, 0 = OFF).
DI 2 ACTUAL
This point indicates the status of bypass Digital Input 2
(1 = ON, 0 = OFF).
DI 3 ACTUAL
This point indicates the status of bypass Digital Input 3
(1 = ON, 0 = OFF).
DI 4 ACTUAL
This point indicates the status of bypass Digital Input 4
(1 = ON, 0 = OFF).
DI 5 ACTUAL
This point indicates the status of bypass Digital Input 5
(1 = ON, 0 = OFF).
DI 6 ACTUAL
This point indicates the status of bypass Digital Input 6
(1 = ON, 0 = OFF).
RO 1 ACTUAL
This point indicates the status of bypass Relay Output 1
(1 = ON, 0 = OFF).
RO 2 ACTUAL
This point indicates the status of bypass Relay Output 2
(1 = ON, 0 = OFF).
RO 3 ACTUAL
This point indicates the status of bypass Relay Output 3
(1 = ON, 0 = OFF).
RO 4 ACTUAL
This point indicates the status of bypass Relay Output 4
(1 = ON, 0 = OFF).
RO 5 ACTUAL
This point indicates the status of bypass Relay Output 5
(1 = ON, 0 = OFF).
BYPASS ALARM This point indicates the current alarm state of the bypass
(1 = ALARM, 0 = OK).
ALARM WORD1
This point is a bit-field indicating active alarms in the
bypass.
ALARM WORD2
This point is a bit-field indicating active alarms in the
bypass.
LAST FAULT
This point is first in the bypass's fault log and indicates the
most recent fault declared.
OK.FAULT BYP
This point indicates the current fault state of the bypass
(1 = FAULT, 0 = OK).
ACH550 E-Clipse Bypass User's Manual
Description
Drive
Parameter
1619
0103, bit 5
0103, bit 4
0103, bit 3
0103, bit 2
0103, bit 1
0103, bit 0
0104, bit 4
0104, bit 3
0104, bit 2
0104, bit 1
0104, bit 0
0308
0309
0401