Embedded fieldbus
Point
AO1 COMMAND
Controls Analog Output 1.
Parameter 1501 must be set to this value for FLN to have this
control.
AO2 COMMAND
Controls Analog Output 2.
Parameter 1507 must be set to this value for FLN to have this
control.
RESET RUN
Commanded by FLN to reset the cumulative run timer (1 =
TIME
RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This "momentary" operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
RESET KWH
Commanded by FLN to reset the cumulative kilowatt-hour
counter (1 = RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This "momentary" operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
PRC PID GAIN
Sets the proportional gain of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
PRC PID ITIM
Sets the integration time of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
PRC PID DTIM
Sets the derivation time of the active Process PID set, as
selected by Point 54, PRC PID SEL (1 = SET2, 0 = SET1).
PRC PID DFIL
Sets the time constant for the error-derivative of the active
Process PID set, as selected by Point 54, PRC PID SEL
(1 = SET2, 0 = SET1).
PRC PID SEL
Selects the active Process PID set (1 = SET2, 0 = SET1).
EXT PID GAIN
Sets the proportional gain of the External PID controller.
EXT PID ITIM
Sets the integration time of the External PID controller.
EXT PID DTIM
Sets the derivation time of the External PID controller.
EXT PID DFIL
Sets the time constant for the error-derivative of the External
PID controller.
LOCK PANEL
Command by FLN to lock the panel and prevent parameter
changes (1 = LOCK, 0 = UNLOCK).
INPUT REF 1
Sets Input Reference 1.
Parameter 1102 must be set to COMM for FLN to control this
value.
INPUT REF 2
Sets Input Reference 2.
Parameter 1106 must be set to COMM for FLN to control this
value.
EXT PID STPT
The setpoint for the External PID controller.
The function of this point requires parameter 4210, PID
Setpoint Select, to be set to 19 (Internal).
FLN Detailed Point Descriptions
Description
ACH550-UH User's Manual
Drive
Parameter
0135
(COMM
VALUE 1)
0136
(COMM
VALUE 2)
4001 (SET1)
4101 (SET2)
4002 (SET1)
4102 (SET2)
4001 (SET1)
4101 (SET2)
4004 (SET1)
4104 (SET2)
4027
4201
4202
4203
4204
1602
4211