ABB ACH550-UH User Manual page 590

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

2-244
Standard enclosure terminals, 208...240 volt units
208...240 Volt
1
HP
Type Code
1
ACH550-BxR-04A6-2
1.5
ACH550-BxR-06A6-2
2
ACH550-BxR-07A5-2
3
ACH550-BxR-012A-2
5
ACH550-BxR-017A-2
7.5
ACH550-BxR-024A-2
10
ACH550-BxR-031A-2
15
ACH550-BxR-046A-2
20
ACH550-BxR-059A-2
25
ACH550-BxR-075A-2
30
ACH550-BxR-088A-2
40
ACH550-BxR-114A-2
50
ACH550-BxR-143A-2
60
ACH550-BxR-178A-2
75
ACH550-BxR-221A-2
100
ACH550-BxR-248A-2
1. "BxR" represents both BCR and BDR.
2. Torque values shown relate to current production. Check component labels on previously installed units for required
tightening torque.
Technical data
Base
Circuit
Circuit
Drive
Breaker
Breaker
Frame
UL Type/
UL Type/
Size
NEMA
NEMA
1 & 12
3R
R1
R1
R1
#8
#8
40 in-lbs
40 in-lbs
R1
R1
R2
R2
R3
#1
#1
50 in-lbs
50 in-lbs
R3
R4
R4
350
350
R4
MCM
MCM
274
274
R6
in-lbs
in-lbs
R6
R6
2 x 500
2 x 500
MCM
MCM
274
274
R6
in-lbs
in-lbs
ACH550 E-Clipse Bypass User's Manual
Power Wiring Data
Disconnect
Disconnect
Motor
Switch
Switch
Terminals
UL Type/
UL Type/
UL Type/
NEMA
NEMA
NEMA
1 & 12
3R
1 & 2
30 in-lbs
#8
#8
7 in-lbs
7 in-lbs
50 in-lbs
#4
#4
18 in-lbs
18 in-lbs
#2/0
120 in-lbs
#1
#1
55 in-lbs
55 in-lbs
#1/0
#1/0
70 in-lbs
70 in-lbs
53 in-lbs
250 MCM
300 in-lbs
300 MCM
300 MCM
275 in-lbs
275 in-lbs
400 MCM
375 in-lbs
2 x 500
2 x 500
2 x 500
MCM
MCM
MCM
274 in-lbs
274 in-lbs
375 in-lbs
2
Motor
Ground
Terminals
Lugs
UL Type/
UL Type/
NEMA
NEMA
3R
1 & 2
#6
#6
#4
30 in-lbs
35 in-lbs
#3
#3
50 in-lbs
#2
50 in-lbs
#2/0
120 in-lbs
#1
#1
53 in-lbs
250 MCM
300 in-lbs
2 x #3/0
400 MCM
250 in-lbs
375 in-lbs
2 x 500
MCM
375 in-lbs
Ground
Lugs
UL Type/
NEMA
3R
#4
35 in-lbs
#2
50 in-lbs
#2/0
375 in-lbs
350 MCM
100 in-lbs

Hide quick links:

Advertisement

Table of Contents
loading