ABB ACH550-UH User Manual page 249

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

ACH550-UH User's Manual
40047
40048
For the Modbus protocol, drive parameters in group 53 report the parameter
mapping to 4xxxx Registers.
Code
5310
5311
5312
5313
5314
5315
5316
5317
5318
5319
5320
Except where restricted by the drive, all parameters are available for both reading
and writing. The parameter writes are verified for the correct value, and for a valid
register addresses.
Note: Parameter writes through standard Modbus are always volatile i.e. modified
values are not automatically stored to permanent memory. Use parameter 1607
PARAM
The ACH550 supports the following Modbus function codes for 4xxxx registers:
03
06
16 (0x10 Hex)
23 (0x17 Hex)
Modbus Register
ACH550
2 LSW
REF
ACH550
2 MSW
REF
EFB PAR 10
Specifies the parameter mapped to Modbus register 40005.
EFB PAR 11
Specifies the parameter mapped to Modbus register 40006.
EFB PAR 12
Specifies the parameter mapped to Modbus register 40007.
EFB PAR 13
Specifies the parameter mapped to Modbus register 40008.
EFB PAR 14
Specifies the parameter mapped to Modbus register 40009.
EFB PAR 15
Specifies the parameter mapped to Modbus register 40010.
EFB PAR 16
Specifies the parameter mapped to Modbus register 40011.
EFB PAR 17
Specifies the parameter mapped to Modbus register 40012.
Reserved.
EFB PAR 19
Holds a copy (in hex) of the
EFB PAR 20
Holds a copy (in hex) of the
.
to save all altered values.
SAVE
Function Code
Read holding 4xxxx registers
Preset single 4xxxx register
Preset multiple 4xxxx registers
Read/write 4xxxx registers
Access
R/W
Maps directly to the Least Significant Word of the DCU
profile's
2. Supported only if BP Parameter
REF
5305 = 1. See drive parameter 0112.
R/W
Maps directly to the Most Significant Word of the DCU
profile's
2. Supported only if BP Parameter
REF
5305 = 1. See drive parameter 0112.
Description
, Modbus register 40001.
CONTROL WORD
, Modbus register 40004.
STATUS WORD
Description
Remarks
Embedded fieldbus
1-245