1-92
Group 10: START/STOP/DIR
This group:
• defines external sources (
and direction changes
• locks direction or enables direction control.
To select between the two external locations use the next group (parameter 1102).
Code Description
1001 EXT1 COMMANDS
Defines external control location 1 (
0 =
– No external start, stop and direction command source.
NOT SEL
1 =
1 – Two-wire Start/Stop.
DI
• Start/Stop is through digital input
• Parameter 1003 defines the direction. Selecting 1003 = 3 (
2 =
1,2 – Two-wire Start/Stop, Direction.
DI
• Start/Stop is through digital input
• Direction control [requires parameter 1003 = 3 (
(
2 activated = Reverse; de-activated = Forward).
DI
3 =
1
,2
– Three-wire Start/Stop.
DI
P
P
• Start/Stop commands are through momentary push-buttons (the
• Start is through a normally open push-button connected to digital input
input
2 must be activated prior to the pulse in
DI
• Connect multiple Start push-buttons in parallel.
• Stop is through a normally closed push-button connected to digital input
• Connect multiple Stop push-buttons in series.
• Parameter 1003 defines the direction. Selecting 1003 = 3 (
4 =
1
,2
,3 – Three-wire Start/Stop, Direction.
DI
P
P
• Start/Stop commands are through momentary push-buttons, as described for
• Direction control [requires parameter 1003 = 3 (
(
3 activated = Reverse; de-activated = Forward).
DI
5 =
1
,2
,3
– Start Forward, Start Reverse and Stop.
DI
P
P
P
• Start and Direction commands are given simultaneously with two separate momentary push-buttons (the
stands for "pulse").
• Start Forward command is through a normally open push-button connected to digital input
the drive, the digital input
• Start Reverse command is through a normally open push-button connected to digital input
the drive, the digital input
• Connect multiple Start push-buttons in parallel.
• Stop is through a normally closed push-button connected to digital input
• Connect multiple Stop push-buttons in series.
• Requires parameter 1003 = 3 (
6 =
6 – Two-wire Start/Stop.
DI
• Start/Stop is through digital input
• Parameter 1003 defines the direction. Selecting 1003 = 3 (
7 =
6,5 – Two-wire Start/Stop/Direction.
DI
• Start/Stop is through digital input
• Direction control [requires parameter 1003 = 3 (
(
5 activated = Reverse; de-activated = Forward).
DI
8 =
– Control Panel.
KEYPAD
• Start/Stop and Direction commands are through the control panel when
• Direction control requires parameter 1003 = 3 (
9 =
1
,2
– Start/Stop/Direction commands through
DI
F
R
• Start forward =
• Start reverse =
• Stop = both
1 and
DI
• Requires parameter 1003 = 3 (
Parameters
Group 10: Start/Stop/Dir
Range
0...14
1) – the configuration of start, stop and direction commands.
EXT
1 (
1 activated = Start;
DI
DI
1 (
1 activated = Start;
DI
DI
3 must be activated prior to the pulse in
DI
3 must be activated during the pulse in
DI
).
REQUEST
6 (
6 activated = Start;
DI
DI
6 (
6 activated = Start;
DI
DI
1 activated and
2 de-activated.
DI
DI
1 de-activated and
2 activated.
DI
DI
2 activated, or both de-activated.
DI
).
REQUEST
1 and
2) for commands that enable start, stop
EXT
EXT
Resolution
1
1 de-activated = Stop).
DI
) is the same as 1003 = 1 (
REQUEST
1 de-activated = Stop).
DI
)] is through digital input
REQUEST
stands for "pulse").
P
1.
DI
) is the same as 1003 = 1 (
REQUEST
)] is through digital input
REQUEST
1.
DI
2.
DI
6 de-activated = Stop).
DI
) is the same as 1003 = 1 (
REQUEST
6 de-activated = Stop).
DI
)] is through digital input
REQUEST
).
REQUEST
1 and
2 combinations.
DI
DI
ACH550-UH User's Manual
Default
1 (
1)
DI
FORWARD
2
DI
1. In order to start the drive, the digital
DI
2.
DI
FORWARD
1
,2
.
DI
P
P
3
DI
1. In order to start
DI
2. In order to start
DI
3.
DI
FORWARD
5.
DI
1 is active.
EXT
S
).
).
P
).