ABB ACH550-UH User Manual page 437

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

ACH550 E-Clipse Bypass User's Manual
Bypass
Parameter
5005
5010
5011
Description
EFB CTRL PROFILE
Selects the communication
profile used by the EFB
protocol.
0 =
ABB DRV LIM
Operation of Control/
Status Words conform to
limited ABB Drives
Profile, as used in
ACH400/550.
1 =
DCU PROFILE
Operation of Control/
Status Words conform to
32-bit DCU Profile.
2 =
ABB DRV FULL
Operation of Control/
Status Words conform to
ABB Bypass Profile, as
used in ACS600/800.
BP PAR10
Sets the response
turnaround time in
milliseconds.
BP PAR11
EFB Protocol Reference
Modbus
N2
FLN
(Read Only Copy, edit in 5305)
(Read Only Copy, edit in 5310)
Not used for Comm setup.
2-91
BACnet
This parameter,
together with
parameter 5017, BP
17, sets BACnet
PAR
Device Object Instance
IDs:
• For the range 1 to
65,535: This
parameter sets the
ID directly (5017
must be 0). For
example, the
following values set
the ID to 49134:
5011 = 49134 and
5017 = 0.
• For IDs > 65,335:
The ID equals
5011's value plus
10,000 times 5017's
value. For example,
the following values
set the ID to 71234:
5011 = 1234 and
5017 = 7.
Embedded fieldbus