Group 01: OPERATING DATA
This group contains drive operating data, including actual signals. The drive sets the
values for actual signals, based on measurements or calculations. You cannot set
these values.
Code Description
0101 SPEED & DIR
The calculated signed speed of the motor (rpm). The absolute value of 0101
0102
.
SPEED
• The value of 0101
• The value of 0101
0102 SPEED
The calculated speed of the motor (rpm).
0103 OUTPUT FREQ
The frequency (Hz) applied to the motor.
0104 CURRENT
The motor current, as measured by the ACH550.
0105 TORQUE
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque.
0106 POWER
The measured motor power in kW.
0107 DC BUS VOLTAGE
The DC bus voltage in V DC, as measured by the ACH550.
0109 OUTPUT VOLTAGE
The voltage applied to the motor.
0110 DRIVE TEMP
The temperature of the drive power transistors in degrees Celsius.
0111 EXTERNAL REF 1
External reference,
0112 EXTERNAL REF 2
External reference,
0113 CTRL LOCATION
Active control location. Alternatives are:
0 =
LOCAL
1 =
1
EXT
2 =
2
EXT
0114 RUN TIME (R)
The drive's accumulated running time in hours (h).
• Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0115 KWH COUNTER (R)
The drive's accumulated power consumption in kilowatt hours.
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
• Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
Parameters
Group 01: Operating Data
Range
-30000...30000 rpm
&
is positive if the motor runs in the forward direction.
SPEED
DIR
&
is negative if the motor runs in the reverse direction.
SPEED
DIR
0...30000 rpm
0.0...500.0 Hz
0.0...1.5 · I
-200.0...200.0%
-1.5...1.5 · P
0...2.5 · V
0...2.0 · V
0.0...150.0 °C
0.0...500.0 Hz /
0...30000 rpm
1, in rpm or Hz – units determined by parameter 9904.
REF
0.0...100.0%
(0.0...600.0% for torque)
2, in %.
REF
0...2
0...9999 h
0...65535 kWh
Resolution
1 rpm
1 rpm
0.1 Hz
0.1 A
2n
0.1%
0.1 kW
n
1 V
dN
1 V
dN
0.1 °C
0.1 Hz / 1 rpm
0.1%
1
1 h
1 kWh