2-42
Recommended control wiring between ACH550 and E-Clipse Bypass to enable Advanced Override 2.
Required for E-Clipse parameter 1708 selections [2] VFD and [3] VFD/BYPASS.
Bypass functions overview
AI1
Switch AI1 in the OFF position.
AI2
Switch AI2 in the ON position.
X1
1
SCR
Signal Cable Shield (screen)
Analog Input AI1
2
AI1
3
AGND
Analog Input Circuit Common
4 +10V
Reference Voltage 10 V DC
5
AI2
Analog Input AI2: FEEDBACK
6
AGND
Analog Input Circuit Common
7 AO1
Analog Output AO1
8 AO2
Analog Output
9 AGND
Analog Output Circuit Common
10
+24V
Auxiliary Voltage Output +24 V DC
11
GND
Auxiliary Voltage Output Common
12
DCOM
Digital Input Common for All
13
DI1
14
DI2
15
DI3
16
DI4
(P 1608: START ENABLE 1: [4] DI4)
17
DI5
(P 1701: OVERRIDE SEL: [5] DI5)
18
DI6
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
ABB ACH550
X2
1
+24V
Auxiliary voltage output +24 V DC
2
+24V
Auxiliary voltage output +24 V DC
3
DCOM
Digital input common for all
4
GND
Auxiliary voltage common
5
DI1
6
DI2
7
DI3
8
DI4
9
DI5
10
DI6
11
RO1C
12 RO1A
13
RO1B
14
RO2C
15 RO2A
16
RO2B
17
RO3C
18 RO3A
19
RO3B
20
RO4C
(P 1410: R04 SELECT: [12] OVERRIDE)
21 RO4A
22
RO4B
23
RO5C
(P 1413: RO5 SELECT: [32] OVRD2 ENAB)
24 RO5A
25
RO5B
ABB E-Clipse Bypass