Embedded fieldbus
Point
FLN LOC REF
Commanded by FLN to temporarily "steal" input reference
control of the drive from its normal source and place it under
FLN control. This functionality is analogous to placing the
drive in HAND mode at the panel, with the reference control
being taken by FLN instead. HAND mode at the panel has
priority over this point. Thus, this point is only effective in
temporarily taking control from the analog inputs or some
other internal control functionality.
DI 1 ACTUAL
Indicates the status of Digital Input 1 (1 = ON, 0 = OFF).
DI 2 ACTUAL
Indicates the status of Digital Input 2 (1 = ON, 0 = OFF).
DI 3 ACTUAL
Indicates the status of Digital Input 3 (1 = ON, 0 = OFF).
DI 4 ACTUAL
Indicates the status of Digital Input 4 (1 = ON, 0 = OFF).
DI 5 ACTUAL
Indicates the status of Digital Input 5 (1 = ON, 0 = OFF).
DI 6 ACTUAL
Indicates the status of Digital Input 6 (1 = ON, 0 = OFF).
RO 1 ACTUAL
Indicates the status of Relay Output 1 (1 = ON, 0 = OFF).
RO 2 ACTUAL
Indicates the status of Relay Output 2 (1 = ON, 0 = OFF).
RO 3 ACTUAL
Indicates the status of Relay Output 3 (1 = ON, 0 = OFF).
RO 4 ACTUAL
Indicates the status of Relay Output 4 (1 = ON, 0 = OFF).
RO 5 ACTUAL
Indicates the status of Relay Output 5 (1 = ON, 0 = OFF).
RO 6 ACTUAL
Indicates the status of Relay Output 6 (1 = ON, 0 = OFF).
AI 1 ACTUAL
Indicates the input level of Analog Input 1.
AI 2 ACTUAL
Indicates the input level of Analog Input 2.
AO 1 ACTUAL
Indicates the output level of Analog Output 1.
AO 2 ACTUAL
Indicates the output level of Analog Output 2.
OK.ALARM
Indicates the current alarm state of the drive
(1 = ALARM, 0 = OK).
OK.MAINT
Indicates the current maintenance state of the drive
(1 = MAINT, 0 = OK).
Maintenance triggers are configured in drive parameter
Group 29.
ALARM WORD1
This point is a bit-field indicating active alarms in the drive.
ALARM WORD2
This point is a bit-field indicating active alarms in the drive.
LAST FAULT
This point is first in the drive's fault log and indicates the most
recent fault declared.
PREV FAULT 1
This point is second in the drive's fault log and indicates the
previous fault declared.
PREV FAULT 2
This point is last in the drive's fault log and indicates the
oldest fault in the log.
OK.FAULT
Indicates the current fault state of the drive
(1 = FAULT, 0 = OK).
ACH550 E-Clipse Bypass User's Manual
FLN Detailed Point Descriptions
Description
Drive
Parameter
0118, bit 2
0118, bit 1
0118, bit 0
0119, bit 2
0119, bit 1
0119, bit 0
0122, bit 2
0122, bit 1
0122, bit 0
0123, bit 2
0123, bit 1
0123, bit 0
0120
0121
0124
0125
0308
0309
0401
0412
0413