ACH550-UH User's Manual
63
EXT PID FBCK
64
EXT PID DEV
65
N/A
66
SPD OUT MIN
67
SPD OUT MAX
68
FLN LOC CTL
69
FLN LOC REF
70
DI 1 ACTUAL
71
DI 2 ACTUAL
72
DI 3 ACTUAL
73
DI 4 ACTUAL
74
DI 5 ACTUAL
75
DI 6 ACTUAL
76
RO 1 ACTUAL
77
RO 2 ACTUAL
78
RO 3 ACTUAL
79
RO 4 ACTUAL
80
RO 5 ACTUAL
81
RO 6 ACTUAL
82
AI 1 ACTUAL
83
AI 2 ACTUAL
84
AO 1 ACTUAL
85
AO 2 ACTUAL
FLN Detailed Point Descriptions
Point
The External PID feedback signal.
The deviation of the External PID output signal from its
setpoint.
Sets the minimum output speed of the drive as a percentage
of the motor nominal rating.
Sets the maximum output speed of the drive as a percentage
of the motor nominal rating.
Commanded by FLN to temporarily "steal" start/stop control
of the drive from its normal source and place it under FLN
control. This functionality is analogous to placing the drive in
HAND mode at the panel, with the control being taken by
FLN instead. HAND mode at the panel has priority over this
point. Thus, this point is only effective in temporarily taking
control from the digital inputs or some other internal control
functionality.
Commanded by FLN to temporarily "steal" input reference
control of the drive from its normal source and place it under
FLN control. This functionality is analogous to placing the
drive in HAND mode at the panel, with the reference control
being taken by FLN instead. HAND mode at the panel has
priority over this point. Thus, this point is only effective in
temporarily taking control from the analog inputs or some
other internal control functionality.
Indicates the status of Digital Input 1 (1 = ON, 0 = OFF).
Indicates the status of Digital Input 2 (1 = ON, 0 = OFF).
Indicates the status of Digital Input 3 (1 = ON, 0 = OFF).
Indicates the status of Digital Input 4 (1 = ON, 0 = OFF).
Indicates the status of Digital Input 5 (1 = ON, 0 = OFF).
Indicates the status of Digital Input 6 (1 = ON, 0 = OFF).
Indicates the status of Relay Output 1 (1 = ON, 0 = OFF).
Indicates the status of Relay Output 2 (1 = ON, 0 = OFF).
Indicates the status of Relay Output 3 (1 = ON, 0 = OFF).
Indicates the status of Relay Output 4 (1 = ON, 0 = OFF).
Indicates the status of Relay Output 5 (1 = ON, 0 = OFF).
Indicates the status of Relay Output 6 (1 = ON, 0 = OFF).
Indicates the input level of Analog Input 1.
Indicates the input level of Analog Input 2.
Indicates the output level of Analog Output 1.
Indicates the output level of Analog Output 2.
Description
1-225
Drive
Parameter
0131
0133
2007
(SCALAR)
2001
(SPEED)
2008
(SCALAR)
2002
(SPEED)
0118, bit 2
0118, bit 1
0118, bit 0
0119, bit 2
0119, bit 1
0119, bit 0
0122, bit 2
0122, bit 1
0122, bit 0
0123, bit 2
0123, bit 1
0123, bit 0
0120
0121
0124
0125
Embedded fieldbus