ABB ACH550-UH User Manual page 420

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

2-74
Code
Name
3004
COMM LOSS
3005
COMM TIME
3006
PHASE LOSS
3007
PHASE SEQ
3008
BYPASS MOL
Group 32: Supervisory Control
Code
Name
3201
SUPER
CTRL
3202
START LVL
3203
STOP LEVEL
3204
START DLY
3205
STOP DLY
3206
FBK LOSS
Parameters
Group 30: Fault Function
Resolution
Range
1
0 = NOT SEL
1 = FAULT
2 = CONST SP7
3 = LAST SPEED
0.1s
0.0 - 600.0s
1
0 = DISABLE
1 = ENABLE
1
0 = DISABLE
1 = ENABLE
1
50 - 150%
Group 32: Supervisory Control
Resolution
Range
1
0 = DISABLE
1 = ENABLE
1%
0 - 100%
1%
0 - 100%
1s
20 - 3600s
1s
20 - 3600s
1
0 = BYP STOP
1 = BYP START
ACH550 E-Clipse Bypass User's Manual
Default
Description
NOT SEL
This parameter serves similar
(0)
purpose as parameter 3018 in
drive which specifies behavior if
Modbus link goes down.
Difference is that this parameter
applies in drive and bypass
modes and if drive node or
bypass node detects a problem.
10.0s
Sets the communication fault
time used with COMM LOSS
parameter.
1
Disable for input phase loss.
1
Disable for input phase
sequence fault.
110%
Motor Overload trip level as % of
ACH550 parameter 9906
MOTOR NOM CURR.
Default
Description
DISABLE
Enable supervisory control in
( 0)
bypass mode.
70%
Value of drive's AI2 that causes
bypass contactor closure.
Applies only in supervisory
mode.
30%
Value of drive's AI2 that causes
bypass contactor opening.
Applies only in supervisory
mode.
40s
Time that close condition must
be present before contactor is
closed.
Applies only in supervisory
mode.
60s
Time that open condition must be
present before contactor is
opened.
Applies only in supervisory
mode.
BYP
Bypass contactor operation if
START
drive link fault, drive AI2 loss or
(1)
excessive cycling.