Input reference select
Using the fieldbus to provide input references to the drive requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Drive Parameter
1102
1103
1106
Reference scaling
Where required,
• Modbus Register
Reference scaling
N2 analog output objects
• The slope of points 60 and 61 in the
Embedded fieldbus
Value
1/
2
8 (
)
Reference set
EXT
EXT
COMM
selection by fieldbus.
SEL
1
8 (
)
Input reference 1 by
REF
SEL
COMM
fieldbus.
2
8 (
)
Input reference 2 by
REF
SEL
COMM
fieldbus.
REFERENCES
in the
40002
in the
ABB control profiles technical data
Setting
ABB DRV
40001
bit 11
can be scaled. See the following, as appropriate:
Modbus protocol technical data
in the
N2 protocol technical data
FLN protocol technical data
ACH550-UH User's Manual
Protocol Reference
Modbus
N2
FLN BACnet
DCU
PROFILE
40031
BO5
26
bit 5
40002
AO1
60
40003
AO2
61
section.
section.
section.
section.
BV13
AV16
AV17