ACH550-PCR/PDR User's Manual
RHTR Temperature
HI / LO Jumper (X1)
(X1 jumper in LO position)
(X1 jumper in HI position)
The alternate (HI) setting further reduces the likelihood
of condensate in high humidity environments.
WARNING! Check the motor and motor wiring insulation before connecting the
ACH550 to line power. Follow the procedure in the ACH550-UH User's Manual on
page 1-23. Before proceeding with the insulation resistance measurements, check
that the ACH550 is disconnected from incoming line power. Failure to disconnect
line power could result in death or serious injury.
Note: For the remainder of the wiring (motor and control wiring) refer to the
ACH550-UH User's Manual.
Heater ON
Temperature
Default Setting
14.4 °C
58 °F
Alternate Setting
17.8 °C
64 °F
UL Type / NEMA 3R
Heater OFF
Temperature
21.4 °C
70.5 °F
24.7 °C
76.5 °C
Input
Power
3-15
Enclosures
Installation