Code Description
8112 LOW FREQ 1
Sets the frequency limit used to stop the first auxiliary motor. The first auxiliary motor stops if:
• Only one (the first) auxiliary motor is running.
• ACH550 output frequency drops below the limit:
8112 - 1.
• Output frequency stays below the relaxed limit
(8112 + 1 Hz) for at least the time: 8116
After the first auxiliary motor stops:
• Output frequency increases by the value =
(8109
START FREQ
• In effect, the output of the speed regulated motor increases to
compensate for the loss of the auxiliary motor.
See the figure, where:
• A = (8109
START FREQ
• B = Output frequency decrease during the stop delay.
• C = Diagram showing auxiliary motor's run status as
frequency decreases (1 = On).
• Grey path = Shows hysteresis – if time is reversed, the path
backwards is not the same. For details on the path for
starting, see the diagram at 8109
Note: 8112
LOW FREQ
• (2007
MINIMUM FREQ
• 8109
START FREQ
8113 LOW FREQ 2
Sets the frequency limit used to stop the second auxiliary motor.
• See 8112
LOW FREQ
The second auxiliary motor stops if:
• Two auxiliary motors are running.
• ACH550 output frequency drops below the limit: 8113 - 1.
• Output frequency stays below the relaxed limit (8113 + 1 Hz) for at least the time: 8116
8114 LOW FREQ 3
Sets the frequency limit used to stop the third auxiliary motor.
• See 8112
LOW FREQ
The third auxiliary motor stops if:
• Three auxiliary motors are running.
• ACH550 output frequency drops below the limit: 8114 - 1.
• Output frequency stays below the relaxed limit (8114 + 1 Hz) for at least the time: 8116
8115 AUX MOT START D
Sets the Start Delay for the auxiliary motors.
• The output frequency must remain above the start frequency limit (parameter 8109, 8110, or 8111) for this time
period before the auxiliary motor starts.
• See 8109
START FREQ
8116 AUX MOT STOP D
Sets the Stop Delay for the auxiliary motors.
• The output frequency must remain below the low frequency limit (parameter 8112, 8113, or 8114) for this time
period before the auxiliary motor stops.
• See 8112
LOW FREQ
Group 81: PFA Control
Range
0.0...500.0 Hz
AUX MOT STOP D
1) - (8112
1).
LOW FREQ
1) - (8112
1)
LOW FREQ
START FREQ
1 value must be between:
) +1.
1
0.0...500.0 Hz
1 for a complete description of the operation.
0.0...500.0 Hz
1 for a complete description of the operation.
0.0...3600.0 s
1 for a complete description of the operation.
0.0...3600.0 s
1 for a complete description of the operation.
Resolution
0.1 Hz
P 8109
.
f
MAX
P 8112
(P 8112)-1
f
MIN
C
1.
0.1 Hz
0.1 Hz
0.1 s
0.1 s
Default
30.0 Hz (US)
f (Hz)
A
B
P 8116
1
0
30.0 Hz (US)
AUX MOT STOP D
30.0 Hz (US)
AUX MOT STOP D
5.0 s
3.0 s
Parameters
1-173