ACH550 E-Clipse Bypass User's Manual
Group 14: Relay Outputs
Code
Name
1401
RO1 SELECT
1402
R1 ON DLY
1403
R1 OFF DLY
1404
RO2 SELECT
1405
R2 ON DLY
1406
R2 OFF DLY
1407
RO3 SELECT
1408
R3 ON DLY
1409
R3 OFF DLY
Group 14: Relay Outputs
Resolution
Range
1
0 = NOT SEL
1 = SYS READY
2 = SYS RUNNING
3 = SYS STARTED
4 = BYPASS SEL
5 = BYPASS RUN
6 = BYPASS FLT
7 = BYP NOT FLT
8 = BYPASS ALRM
9 = DRIVE FAULT
10 = DRV NOT FLT
11 = DRIVE ALARM
12 = OVERRIDE
13 = BYPASS HAND
14 = BYPASS OFF
15 = BYPASS AUTO
16 = COMM CTRL
17 = SYS ALARM
18 = BYP FLT/ALM
19 = BYP OVERLD
20 = BYP UNDERLD
21 = PCB OVERTMP
22 = SYS UNDERLD
23 = SYSTEM FLT
24 = SYS FLT/ALM
25 = SYS EXT CTL
26 = SYS OVERLD
27 = CONTACT FLT
28 = SYS NOT FLT
29 = DRV LNK ERR
30 = EXT COMM LS
31 = OVRD2 STOP
32 = OVRD2 ENAB
0.1 sec
0-3600.0s
0.1 sec
0-3600.0s
1
See RO 1 Select.
0.1 sec
0-3600.0s
0.1 sec
0-3600.0s
1
See RO 1 Select.
0.1 sec
0-3600.0s
0.1 sec
0-3600.0s
Default
Description
BYP NOT
Selects function for digital output.
FLT
Define the event or condition that
(7)
activates relay 1.
0s
Delay from active state to active
output.
0s
Delay from inactive state to
inactive output.
SYS
RUNNING
(2)
0s
Delay from active state to active
output.
0s
Delay from inactive state to
inactive output.
SYS
STARTED
(3)
0s
Delay from active state to active
output.
0s
Delay from inactive state to
inactive output.
2-67