ABB ACH550-UH User Manual page 22

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

1-18
Wiring overview
Conduit kit
Wiring R1...R6 drives with the UL type 1 Enclosure requires a conduit kit with the
following items:
• conduit box
• screws
• cover
The kit is included with UL type 1 Enclosures.
Wiring requirements
WARNING! Ensure the motor is compatible for use with the ACH550. The ACH550
must be installed by a competent person in accordance with the considerations
defined in
sales or service office.
As you install the wiring, observe the following:
• There are two sets of wiring instructions – one set for each enclosure type (UL
type 1 and UL type 12). Be sure to select the appropriate procedure.
• For the power connection points on the drive see the
section below.
• Use separate, metal conduit runs to keep these three classes of wiring apart:
– Input power wiring.
– Motor wiring. (Use a separate, metal conduit run for each motor)
– Control/communications wiring.
• When installing input power and motor wiring, refer to the following, as
appropriate:
U1, V1, W1*
PE
U2, V2, W2
* The ACH550 -xx-xxxx-2 (208...240V series) can be used with a single phase supply, if output
current is derated by 50%. For single phase supply voltage connect power at U1 and W1.
• To locate input power and motor connection terminals, see
starting on page 1-20. For specifications on power terminals, see
connection terminals
• For corner grounded TN systems, see section
networks
• For IT systems, see section
• For frame size R6, see
1-307
Installation
Preparing for installation
Terminal
Description
3-phase power supply input
Protective Ground
Power output to motor
on page 1-307.
on page 1-305.
Power terminal considerations – R6 Frame size
to install the appropriate cable lugs.
on page 1-10. If in doubt, contact your local ABB
Specifications and Notes
Input power connections
Ground connections
Motor connections
Unsymmetrically grounded
on page 1-306.
Floating networks
ACH550-UH User's Manual
Connection diagrams
on page 1-301.
on page 1-305.
on page 1-309.
Connection diagrams
Drive's power
on page