N2 analog output objects – bypass
The following table lists the N2 Analog Input objects defined for the ABB E-Clipse
bypass.
Number
AO1
AO2
AO3
N2 binary input objects – bypass
The following table lists the N2 Binary Input objects defined for the ABB E-Clipse
bypass.
Number
BI1
BI2
BI3
BI4
BI5
Object
ALARM WORD 2
HAND OFF AUTO
INPUT VOLT
PCB TEMP
KW HOURS
RUN TIME
A-B VOLT
B-C VOLT
C-B VOLT
Object
BYP RUNDLY
MB PARAM
MB DATA
Object
SYSTEM READY
SYSTEM ENABLED
SYSTEM STARTED
SYSTEM RUNNING
N2 LOCAL MODE
N2 Analog Inputs:
Bypass
Scale
Parameter
Factor
0309
1
0102
1
0105
0.1
0106
1
0108
1
0111
1
0112
1
0113
1
N2 Analog Inputs:
Bypass
Scale
Parameter
Factor
1614
1
NA
1
NA
1
N2 Binary Inputs:
Drive Parameter
Status Word
1 = Ready
Status Word
1 = Enabled
Status Word
1 = System Started
Status Word
1 = System Running
Status Word
1 = N2 Local
2-119
Units
Range
Alarm mask
(see bypass
manual
description of
parameter
0309)
0=Off, 1=Hand,
2=Auto
V
Average of line-
line input
voltage
°
C
Temperature of
bypass board
kWh
Bypass-mode
kilowatt hours
HR
0...65535
V
Phase A -
Phase B voltage
V
Phase B -
Phase C voltage
V
Phase C -
Phase A voltage
Units
Range
s
0...300
None
0...65535
None
0...65535
Range