2-164
Note: For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays & relinquish
defaults.
Analog value object instance summary – drive
The following table summarizes the Analog Value Objects supported:
Instance
ID
AV0
AV1
AV2
AV3
AV4
AV5
AV6
AV7
AV8
AV9
AV10
AV11
AV12
Embedded fieldbus
Object Name
OUTPUT
This object indicates the calculated motor
SPEED
speed in RPM. The corresponding drive
parameter is 0102.
OUTPUT FREQ This object indicates the output
frequency applied to the motor in Hz. The
corresponding drive parameter is 0103.
DC BUS VOLT
This object indicates the drive's DC bus
voltage level. The corresponding drive
parameter is 0107.
OUTPUT VOLT
This object indicates the AC output
voltage applied to the motor. The
corresponding drive parameter is 0109.
CURRENT
This object indicates the measured
output current. The corresponding drive
parameter is 0104.
TORQUE
This object indicates the calculated motor
output torque as a percentage of nominal
torque. The corresponding drive
parameter is 0105.
POWER
This object indicates the measured
output power in kW. The corresponding
drive parameter is 0106.
DRIVE TEMP
This object indicates the measured
heatsink temperature in °C. The
corresponding drive parameter is 0110.
KWH (R)
This object indicates, in kW hours, the
drive's accumulated energy usage since
the last reset. The value can be reset to
zero. The corresponding drive parameter
is 0115.
KWH (NR)
This object indicates the drive's
accumulated energy usage in MW hours.
The value cannot be reset.
PRC PID FBCK
This object is the Process PID feedback
signal. The corresponding drive
parameter is 0130.
PRC PID DEV
This object is the Process PID output
signal's deviation from its setpoint. The
corresponding drive parameter is 0132.
EXT PID FBCK
This object is the External PID feedback
signal. The corresponding drive
parameter is 0131.
ACH550 E-Clipse Bypass User's Manual
Description
Present Value
Units
Access Type
RPM
R
Hertz
R
Volts
R
Volts
R
Amps
R
Percent
R
Kilowatts
R
°C
R
kWh
W
MWh
R
Percent
R
Percent
R
Percent
R