ABB ACH550-UH User Manual page 227

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

ACH550-UH User's Manual
30
CURRENT LIM
31
ACCEL TIME 1
32
DECEL TIME 1
33
HANDAUTO
ACT
34
ENA.DIS ACT
35
ENA.DIS CMD
36
FLN LOC ACT
37
FLN CTL SRC
38
FLN REF1 SRC
39
FLN REF2 SRC
40
RO1 COMMAND Controls the output state of Relay 1.
41
RO2 COMMAND Controls the output state of Relay 2.
42
RO3 COMMAND Controls the output state of Relay 3.
43
RO4 COMMAND Controls the output state of Relay 4. Access to relay 4 require
44
RO5 COMMAND Controls the output state of Relay 5. Access to relay 5 require
45
RO6 COMMAND Controls the output state of Relay 6. Access to relay 6 require
FLN Detailed Point Descriptions
Point
Sets the output current limit of the drive.
Sets the acceleration time for Ramp 1.
Sets the deceleration time for Ramp 1.
Indicates whether the drive is in Hand or Auto control
(1 = HAND, 0 = AUTO).
Indicates the status of the Run Enable command, regardless
of its source (1 = ENABLE, 0 = DISABL).
Commanded by FLN to assert the Run Enable command
(1 = ENABLE, 0 = DISABL).
Parameter 1601 must be set to COMM for FLN to have this
control.
Indicates if the drive has been placed in "FLN LOCAL" mode
by commanding either point 68 (FLN LOC CTL) or point 69
(FLN LOC REF). Commanding either of these points to FLN
(1) "steals" control from its normal source and places in under
FLN control.
Note that the HAND mode of the panel has priority over FLN
local control.
Indicates if FLN is a source for control inputs
(1 = YES, 0 = NO).
Note that this status point is true if any of the following control
inputs are from FLN: Run/Stop, Ext1/2 Select or Run Enable.
Indicates if FLN is the source for speed reference 1
(1 = YES, 0 = NO).
Indicates if FLN is the source for speed reference 2
(1 = YES, 0 = NO).
Parameter 1401 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
Parameter 1402 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
Parameter 1403 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
ACH550 option OREL.
Parameter 1410 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
ACH550 option OREL.
Parameter 1411 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
ACH550 option OREL.
Parameter 1412 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
Description
1-223
Drive
Parameter
2003
2202
2203
0134, bit 0
0134, bit 1
0134, bit 2
0134, bit 3
0134, bit 4
0134, bit 5
Embedded fieldbus