110 Guidelines for planning the electrical installation
Install the protective component as close to the inductive load as possible. Do not install
protective components at the relay outputs.
1
Relay output
2
Varistor
3
RC filter
4
Diode
Limiting relay output maximum voltages at high installation
altitudes
See
Isolation areas, R1...R5 (page 294)
Implementing a motor temperature sensor connection
WARNING!
IEC 61800-5-1 requires double or reinforced insulation between live parts and
accessible parts when:
•
the accessible parts are not conductive, or
•
the accessible parts are conductive, but not connected to the protective earth.
Obey this requirement when you plan the connection of the motor temperature
sensor to the drive.
To connect a motor temperature sensor and other similar components to the drive, you
have four alternatives:
1. If there is double or reinforced insulation between the sensor and the live parts of
the motor, you can connect the sensor directly to the inputs of the drive.
230 V AC
1
230 V AC
+ 24 V DC
and
Isolation areas, R6...R9 (page
2
3
4
295).