Section 5847
Issue AL, July 24, 2006
Configuring the Nodes
Page 5-12
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Uploading the Configuration from a PC to the LMS1000 using TFTP
a) Start a separate TFTP client session on the host from which the
configuration file is transferred.
b) Log onto the system using the default level six password (6).
c) Enter the command UPLOAD TFTP, then press ENTER. The following
will be displayed.
UPLOAD using TFTP
d) After seeing the above prompt, start the upload process from the client.
DO NOT ATTEMP THE UPLOAD UNTIL THE PROMPT ABOVE IS
DISPLAYED.
1) Enter the NODE LIST command and verify all nodes that were previously present
are still present.
Note: Node numbers and names will NOT be the same as before. Verify the
nodes using the neuron ID and other node parameters.
2) Enter the NODE CONFIG command and configure the node numbers and names
using the information recorded earlier.
Chapter 5. Troubleshooting and Repairing LMS1000