RETRIEVE-CONDITION
(RTRV-COND-{EQPT|ALL})
Referenced In: TR-NWT-000833, Issue 5; pg. 4-257
General Description: Instructs LMS1000 to send the current state and standing
condition (alarm or status) associated with one or more equipment units, facilities, etc.
within LMS1000.
In addition, it may be used to summarize the status of the LMS1000 by providing entity
states.
Related Messages: REPORT CONDITION EQUIPMENT
LMS1000 Access Level: 1
LMS1000 Equivalent: None
LMS1000 Input Format Variations: The command code modifier COM is not
supported.
<aid>
Specifying a value of ALL for the access identifier (<aid>) parameter requests retrieval of
conditions for all access identifiers of the type defined by the command code modifier.
Use of the command code modifier ALL results in retrieval of all conditions in the
LMS1000. If the command code modifier is ALL, the value of the access identifier must
be ALL. A NULL value is not permitted for this parameter. Invalid values received for
this parameter return an error response with the error code IIAC.
<typereq>
Specifies the type of condition or state to be retrieved. A valid value can be any condition
type (<condtype>) parameter. Values are derived from the CONDITION TYPE attribute
of the LMS1000 channel or limit configuration with which the alarm condition is
associated. A NULL value causes all condition types to be retrieved. Invalid values for
this parameter return an error response with the error code IDNV.
<locn>
This parameter does not apply to LMS1000. The only valid value for this parameter is
NULL. Invalid values for this parameter return an error response with the error code
INUP.
<dirn>
This parameter does not apply to LMS1000. The only valid value for this parameter is
NULL. Invalid values for this parameter return an error response with the error code
INUP.
<tmper>
Page 3-346
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Chapter 3. Commands
User Instructions

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents