Emerson LMS1000 User Instructions page 231

Monitoring system
Table of Contents

Advertisement

User Instructions
Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
[LVD 4B]
___________________________________________________________________________________
Command<1>: SCAN V SYSTEM
VORTEX SYSTEM STATUS AS OF xx:xx:xx ON xx/xx/xx.
Chan
Description
A9001 Vortex System Voltage
A9002 Vortex System Current
A9006 Vortex Shunt01 Current
A9007 Vortex Shunt02 Current
A9010 Vortex Shunt05 Current
A9011 Vortex Shunt06 Current
B9009 Vortex PCU Emergency Stop
B9024 Vortex PCU High AC Line
B9010 Vortex System Fuse
B9011 Vortex All AC Off
B9014 Vortex LVDs Inhibited
B9015 Vortex System Major
B9016 Vortex System Minor
___________________________________________________________________________________
Command<1>: SCAN V SUBSYSTEM
VORTEX SUBSYSTEM STATUS AS OF xx:xx:xx ON xx/xx/xx.
Chan
Description
A9022 Vortex Subsystem Voltage
A9023 Vortex Subsystem Current
A9008 Vortex Shunt03
A9009 Vortex Shunt04
B9021 Vortex Subsystem Fuse
B9022 Vortex Subsystem Major
B9023 Vortex Subsystem Minor
___________________________________________________________________________________
Command<1>: SCAN V MCA
VORTEX MCA STATUS AS OF xx:xx:xx ON xx/xx/xx.
Description
Board Fail
Shelf fuse
A/D No System Voltage Input
A/D No Sense Lead Voltage Input
A/D No Subsystem Voltage Input
Display Fail
___________________________________________________________________________________
Command<1>: SCAN V LVD
VORTEX LVD STATUS AS OF xx:xx:xx ON xx/xx/xx.
Description
LVD 1A
LVD 1B
LVD 2A
LVD 2B
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
[active]
Value
Units
Alarm Status
+50.3
VDC
[None]
[High Voltage #1]
[High Voltage #2]
[Battery On Discharge]
[50% Battery On Discharge]
+800
Amps
[None/Overcurrent]
+200
Amps
[None/Fail]
+200
Amps
[None/Fail]
+200
Amps
[None/Fail]
+200
Amps
[None/Fail]
[None/Active]
[None/Active]
[None/Active]
[None/Active]
[None/Active]
[None/Active]
[None/Active]
Value
Units
+50.9
VDC
[High Voltage]
[Low Voltage]
+400
Amps
+200
Amps
+200
Amps
[None/Active]
[None/Active]
Alarm Status
active
active
active
active
active
active
Alarm Status
[inhibited/failed/active/inactive]
[inhibited/failed/active/inactive]
[inhibited/failed/active/inactive]
[inhibited/failed/active/inactive]
Chapter 3. Commands
Issue AL, July 24, 2006
Alarm Status
[None]
[None/Overcurrent]
[None/Fail]
[None/Fail]
[None/Active]
Section 5847
Page 3-149

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents