Emerson LMS1000 User Instructions page 146

Monitoring system
Table of Contents

Advertisement

Section 5847
Issue AL, July 24, 2006
Condition Type:
Limit 3 Condition Description:
THIS VOLTAGE IS LOW
Condition Description:
THIS CURRENT IS LOW
Limit 4 Enabled: Yes
Limit 4 Enabled (Y or N):
Limit 4 Value: 40.00
Limit 4 Value: 100
Limit 4 Type: L
Limit 4 Type is High or Low (H or L):
Limit 4 Name: LVA2
Limit 4 Name: BELOW 100
Limit 4 Notification Code: MN
Limit 4 Notification Code:
Limit 4 Service Effect Code: NSA
Limit 4 Service Effect Code:
Limit 4 Alarm Class Number: 2
Condition Type: TOOLOW
Condition Type:
Limit 4 Condition Description:
THIS VOLTAGE IS TOO LOW
Condition Description:
THIS CURRENT IS TOO LOW
Unit Text: VOLT
Unit Text: AMPS
Off Delay Time: 0s
Off Delay Time:
On Delay Time: 0s
On Delay Time: 15
Save changes (Y or N): Y
Enter Program Line:
F0001=A0001+A0002+A0003
___________________________________________________________________________________
Command<6>: CONFIG R0001
RELAY CHANNEL CONFIGURATION AS OF 07:35:40 ON 01/01/01.
Chan
Description
R0001 Relay Channel 1
Sub-access ID
RELAY1
Condition Description
THIS IS RELAY CHANNEL R01'S CONDITION DESCRIPTION
CONTROL PROGRAM:
R0001=B0001
Channel active (Y or N): Y
Name: Relay Channel 1
Name:
Sub-access Identifier: RELAY1
Sub-access Identifier:
Alarm Type: Y
Alarm Type (Y or N):
System Alarm Report mode: Y
System Alarm Report mode (Y or N):
Alarm Class Number: 0
Condition Type: HIGH
Condition Type:
Page 3-64
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Act Alm Rpt Class Set ACO Cycle Off-Dly-On
Y
Y
Y
Ctrltype
Condtype
HIGH
2
Chapter 3. Commands
N
N
0m
0s
Ntfc
Svef
CR
SA
User Instructions
0s

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents