CONNECT

Description: Activates the Gateway port.
Command Level: 4
Syntax: CONNECT
Comments: Allows the LMS1000 to emulate a "dumb" RS-232 asynchronous terminal
interface. When activated, user input through either a local or remote LMS1000 port is
directed to the customer equipment connected to the LMS1000 Gateway port. To exit
and return to the LMS1000 command prompt, press CTRL-C twice. The second CTRL-C
must follow the first within a one second time interval.
Notes: User must be familiar with the command set and operation of the customer
equipment connected to the LMS1000 Gateway port.
Possible data loss may occur if the LMS1000 Gateway port data rate does not match that
of the local or remote terminal being used to access the customer equipment via
LMS1000.
The LMS1000 alarm reports will not be processed while the Gateway feature is active
and a remote terminal is being used.
In normal LMS1000 command mode operation, the LMS1000 echoes characters back to
the user's terminal. This is not done in the Gateway mode, and must be a function
(echoing) of the customer equipment connected to the LMS1000 Gateway port.
This program is automatically exited and the User is returned to the LMS1000 command
prompt if the user timeout period is exceed. If user timeout occurs during a remote
communication session, the communication link is automatically terminated.
Related Commands: SET GATEWAY
Example:
If the Gateway port is available for access when the CONNECT command is issued, the User is prompted
as follows. Note that the Warning message is only displayed when using the LMS1000 modem port.
Command<4>: CONNECT
WARNING!!! ALARM REPORTS CANNOT BE PROCESSED
WHILE GATEWAY SESSION IS ACTIVE
GATEWAY port active
Press <CTRL-C><CTRL-C> to exit
>
<cursor
If the Gateway port is in use by another User, the requesting User will be prompted as follows:
GATEWAY Port Busy – Try Again
Command<4>:
Page 3-68
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Chapter 3. Commands
User Instructions

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents