Issue AL, July 24, 2006
INITIALIZE SYSTEM
(INIT-SYS)
Referenced In: TR-NWT-000833, Issue 5; pg. 4-145
General Description: Instructs LMS1000 to initialize its system processor and/or
associated subsystems.
This command may contain various levels of initialization. The highest level is a cold
restart which is equivalent to a power-up reset. The level of initialization is specified by a
data parameter within the command string.
An entry is made in the LMS1000's event log indicating this command was executed by
the current sessions user. The event description indicates that the system was initialized
to the specified level.
Related Commands: None
LMS1000 Access Level: 6
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: None
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter identifies the equipment unit that is to be
initialized. A value of ALL for this parameter denotes the system processor, and is the
only value which is supported. A NULL value is not permitted for this parameter. Invalid
values received for this parameter return an error response with the error code IIAC.
<ph>
This parameter specifies the level of initialization to be performed. The value of <ph>
must be an integer greater than or equal to zero. The lowest value (0) is the lowest level
of initialization, and the highest value specifies a cold restart initialization.
Valid values for this parameter and the level of initialization associated with them are
listed below.
Page 3-330
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
10
Clear alarm log and event log.
20
Clear alarm log and event log, and hour-average/max-min peak statistics of
all analog and function channels.
50
Clear all channels which have been ACOed.
51
Clear all control channels (relay, LED) which have been forced on manually.
60
Clear all channels which have been ACOed, and all control channels (relay,
LED) which have been forced on manually.
Chapter 3. Commands
Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
User Instructions