Section 5847
Issue AL, July 24, 2006
INHIBIT-MESSAGE-ALL
(INH-MSG-ALL)
Referenced In: TR-NWT-000833, Issue 5; pg. 4-117
General Description: Disables LMS1000 transmission of automatic messages.
Selective disabling of messaging is not implemented in LMS1000. Unreported alarms
and events that occur while autonomous messaging is inhibited are reported via the
proper message type (REPORT ALARM or REPORT EVENT) when autonomous
messaging is re-enabled.
This command disables autonomous messaging for all LMS1000 user's whose REPORT
DEVICE attribute is X25. When executed, the command sets the REPORT MODE
attribute of these users' LMS1000 user configuration to OFF.
An entry is made in the LMS1000's event log indicating this command was executed by
the current sessions user. The event description indicates that automatic messaging was
disabled.
Related Commands: None
LMS1000 Access Level: 6
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: None
LMS1000 Input Format Variances: Command code modifiers other than ALL are not
supported by LMS1000.
<aid>
The access identifier (<aid>) parameter can only be the value ALL. Invalid values
received for this parameter return an error response with the error code IIAC.
<ntfcncde>, <condtype>, <tmper>
These parameters are not implemented in LMS1000. The only valid value for these
parameters are NULL.
response with the error code INUP.
LMS1000 Response Format Variances: None
Page 3-326
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Invalid values received for these parameters return an error
Chapter 3. Commands