Section 5847
Issue AL, July 24, 2006
SET USERS
Description: Allows tailoring of the alarm reporting features of the system to each of the
eight users.
Command Level: 6
Syntax: SET USERS [n]
Comments: The configuration of the user selected is first displayed. Information such
as the name of the user, the password of the user, the access level of the user, whether
or not the user has selected the callback feature, the primary phone number, valid days
and hours of the primary phone number, the alternate phone number, Primary Email, and
Alternate Email. Additional information includes whether the user is configured for the
report device, status of the report mode, the report retry time interval, and whether the
user is configured for the occurred alarm report, the retired alarm report, the persistent
alarm report, the persistent alarm report period, the daily report, and the daily report
command and time.
When callback is selected, additional security is obtained for remote access. After
receiving a password from a remote terminal (over the phone line) the system will hang
up and call either the primary or alternate phone number to obtain access remotely. The
phone number selected will be based on the valid time and day.
If the report mode is set to OFF, none of the reporting functions for this user will be active
regardless of their setting.
The report retry time is the number of minutes that the system will wait before attempting
to contact the user with a callback or user alarm report if there was no answer or a busy
signal during the first try (0-1440 minutes, with 0 representing no retry). (This retry time
has no effect on System Alarm Reporting.) The system will continue to try until someone
calls the system and logs on as the associated user.
When the occurred alarm report is set to YES, the user will receive a call if any new
alarms occur on his channels. If the retired alarm report is set to YES, this user will
receive a call when those alarms have cleared.
If the persistent alarm reporting function is selected, the system will continue to report this
alarm until it has been cleared. The interval between reports for this function is set by the
persistent alarm reporting period.
When the daily report is selected, the user will receive a customized report at a specified
time each day.
A user cannot de-activate himself or change his own access level.
Notes: none
Related Commands: USERS, SET PHONE, SET EMAIL, SET CHANNELS, SET
SYSTEM
Example:
Command<6>: set user
Page 3-236
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
SE US [n]
Chapter 3. Commands
User Instructions

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents