Set Lps System Fltvolt - Emerson LMS1000 User Instructions

Monitoring system
Table of Contents

Advertisement

User Instructions
Spec. Nos. 586505000 and 5865055000 (Model LMS1000)

SET LPS SYSTEM FLTVOLT

Description: Sets the LPS "float output voltage" value.
Command Level: 6
Syntax: SET LPS SYSTEM FLTVOLT
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The MCA does not allow an adjustment which could result in a service
interruption. Refer to the LPS instruction manual's float voltage adjustment procedure for
details.
The following message is displayed if the setting was not accepted by the MCA.
Not Changed!
Related Commands: none
Example:
Command<6>: set lps flt
Float Voltage: 52.08 VDC
Float Voltage: 52.1
New Float Voltage Accepted.
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SE LP SY FL
Chapter 3. Commands
Section 5847
Issue AL, July 24, 2006
Page 3-189