Set Eff - Emerson LMS1000 User Instructions

Monitoring system
Table of Contents

Advertisement

User Instructions
Spec. Nos. 586505000 and 5865055000 (Model LMS1000)

SET EFF

Description: Permits configuration of the energy management option, if furnished.
Command Level: 5 and 6. A user with access to level 5 commands is only allowed to
enter a Y or N at the RECTIFIER EFFICIENCY ROUTINE (Y or N) prompt. This enables
or disables energy management operation. A user with access to level 6 commands is
required to enter the additional parameters.
Syntax: SET EFF
Comments: Parameters include the status of energy management, active or disabled,
and the analog input number of the plant voltage input. Other parameters displayed
include Base Rectifier Cycle Period, Percent of system capacity at which to turn off a
rectifier, and Percent of system capacity at which to turn on a rectifier. After display of
the current parameters, the data may be changed if required.
Notes: Use of this command generates an entry into the Event Log. Not available in an
LPS Power System.
Related Commands: EFF
Example:
Command<6>: set eff
RECTIFIER EFFICIENCY ROUTINE DISABLED
Plant Voltage Input = A0001
Base Rectifier Cycle Period: 1 day
Percent of system capacity at which to turn off a rectifier: 0.970
Percent of system capacity at which to turn on a rectifier: 0.970
Plant Voltage Input = A9001
Enter Base Rectifier Cycle Period (1-365 days): 30
Percent of system capacity at which to turn off a rectifier (0.90-0.99): .93
Percent of system capacity at which to turn on a rectifier (0.97-0.99): .98
Save changes (Y or N):
RECTIFIER EFFICIENCY ROUTINE (Y or N): y
___________________________________________________________________________________
Command<5>: set eff
RECTIFIER EFFICIENCY ROUTINE DISABLED
Plant Voltage Input = A0001
RECTIFIER EFFICIENCY ROUTINE (Y or N): y
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SE EF
n
Chapter 3. Commands
Section 5847
Issue AL, July 24, 2006
Page 3-165