Fuse [Breaker] [Plug In] nn-01 Alarm
through
Fuse [Breaker] [Plug In] nn-47 Alarm
Alarm Log Sub-ID Entries
Bnnnn.09 Fuse / Circuit Breaker Alarm
Bnnnn.11 Shunt Overcurrent Alarm
Bnnnn.12 Unknown Element Alarm
Note that there are no even channel numbers
for distribution elements. Each element takes
Bnn01
up two positions per pole. The channel
through
number for the element is the lowest position
Bnn48
number used. For example: For a single pole
element in distribution panel #2 in position 25
and 26, channels are A0125 and B0125. For a
double pole element in positions 27-30,
channels are A0127 and B0127. For a triple
pole element in positions 31-36, channels are
A0131 and B0131. For a quad pole element in
positions 37-44, channels are A0137 and
B0137.
Bay nn Status
Alarm Log Sub-ID Entries
Bnn49.09 Router Processor Fail
Bnn49.10 Router Communications Fail
Bnn49.11 Router External Voltage Fail
Bnn49.12 Router Internal Voltage Fail
Bnn49.13 Router Firmware Fail
Bnn49.17 Distr. Panel #1 Processor Fail
Bnn49
Bnn49.18 Distr. Panel #1 Communications Fail
Bnn49.19 Distr. Panel #1 A/B Feed Change
Bnn49.20 Distr. Panel #1 Unknown Elements
Bnn49.21 Distr. Panel #1 Firmware Fail
Bnn49.25 Distr. Panel #2 Processor Fail
Bnn49.26 Distr. Panel #2 Communications Fail
Bnn49.27 Distr. Panel #2 A/B Feed Change
Bnn49.28 Distr. Panel #2 Unknown Elements
Bnn49.29 Distr. Panel #2 Firmware Fail
I/O Board bb-ss Alarm (bb = LPS Bay #, ss =
LPS Bay Slot #)
Alarm Log Sub-ID Entries
Bnn50.09 CAN I/O Processor Fail
Bnn50
Bnn50.10 CAN I/O Communications Fail
Bnn50.11 CAN I/O Duplicate Node
Bnn50.12 Shunt Output Overcurrent Alarm
Bnn50.13 Shunt Input Overcurrent Alarm
Table 2-3 (cont'd from previous page, cont'd on next page)
LPS Interface Analog and Binary Channels
For LPS Bay Nodes (nn = 1-20)