Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
ALLOW-MESSAGE-ALL
(ALW-MSG-ALL)
Referenced In: TR-NWT-000833, Issue 5; pg. 4-39
General Description: Enables the system to resume transmission of automatic
messages after being placed in the inhibit message mode.
Selective enabling of messaging is not implemented in LMS1000. Unreported alarms
and events which have occurred since messaging was inhibited and which have been
written over by a more recent alarm or event (this occurs after two hundred entries) are
not reported. All other unreported alarms and events are reported via the proper
autonomous message type (REPORT ALARM or REPORT EVENT).
This command enables autonomous messaging for all LMS1000 users whose REPORT
DEVICE attribute is X25. When executed, the command sets the REPORT MODE
attribute of these users' LMS1000 user configuration to TL1.
An entry is made in the LMS1000's event log indicating this command was executed by
the current sessions user. The event description indicates that automatic messaging was
enabled.
Related Commands: None
LMS1000 Access Level: 6
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: None
LMS1000 Input Format Variation: Command code modifiers other than ALL are not
supported by LMS1000.
<aid>
The access identifier (<aid>) parameter can only be the value ALL. Invalid values
received for this parameter return an error response with the error code IIAC.
<ntfcncde>, <condtype>, <tmper>
These parameters are not implemented in LMS1000. The only valid value for these
parameters are NULL. Invalid values received for this parameter return an error
response with the error code INUP.
LMS1000 Response Format Variation: None
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Chapter 3. Commands
Section 5847
Issue AL, July 24, 2006
Page 3-317

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents