Parameter Description - Basic Set Up
f) Binary coded set speed selection LF.02 = bnSPd
76
Once in run mode, the drive must see a serial communication
request at the X6C serial port at minimum every 50mSec. If not
the drive will trigger an E.BUS fault.
Clearing an E.BUS error while in serial com mode. When in this
mode, if the controller stops communication with the drive, it
may not be possible to clear the E.BUS fault and view other
parameters. Therefore the following can be used to override
the error such that trouble shooting can occur.
While the display shows E.BUS press and hold both the ENT
and the START key. The display will show the previously
displayed parameter and allow navigation of the parameters.
The internal fault will not reset until the serial communication
has been reestablished
Binary speed setting uses preset digital values in the drive as com-
mand speeds. The drive creates the driving profile between selected
speeds. The inputs are binary coded to allow up to seven speeds.
Additionally in this mode, more advanced and multiple profiles can
be established. See parameters LF.41...LF.56. One speed can be
pre-defined as an emergency run speed in which the drive operates
automatically under emergency operation conditions. See parameter
LF.61 for more details.
Speed =0
S
Leveling
S
High Leveling
S
Inspection
S
High
S
Intermediate_1
S
Intermediate_2
S
Intermediate_3
Symbol:
X2A.10 X2A.11 X2A.12 X2A.13
x
0
0
x
1
0
x
0
1
x
1
1
x
0
0
x
1
0
x
0
1
x
1
1
1 =
Input is active
0 =
Input is not active
X =
Setting has no effect or don't care
Para.
0
0
LF.41
0
LF.44
0
LF.43
1
LF.42
1
LF.45
1
LF.46
1
LF.47