Parameter Description - Basic Set Up
Selected motor
Drive fault auto reset
78
This parameter displays the current mode of operation, open or closed
loop, geared or gearless, induction motor, synchronous motor. The
parameter is read only.
Possible displays:
ICLSd
= Closed loop induction
I9LSS
= Closed loop induction gearless
PCLSd
= Closed loop permanent magnet
P9LSS
= Closed loop permanent magnet gearless
With LF. 5 all drive faults can be automatically reset.
The number adjusted in this parameter determines how many times
per hour the elevator drive will automatically reset faults. Before
resetting the fault, the drive will wait 4 seconds to allow everything
to stop or stabilize. It is not fault specific, so with the default setting
of 5, if the drive experiences 6 different faults in one hour the unit
will latch the last fault and not reset. See parameter LF.8 for fault
history information.
Unit:
1
Value range:
0...10
Default setting:
5
Note: a setting of "0"