The used semiconductors and components of KEB are developed and dimensio- ned for the use in industrial products. If the KEB COMBIVERT is used in machi- Use under spe-...
Analog Input ±10 V variable General Each of the interface cards delivered by KEB include two interfaces. As there are numerous different combinations available each interface will be described by means of separate in- structions. The instruction comprises the installation of the interface card, the connection as well as the start-up of a suitable encoder. Further information and the parameter adjust- ments are described in the application manual for the inverter/servo.
With the default trimming an accuracy of 2 % is reached with the installation of the analog card. A trimming between control card and option is required for a higher accuracy. An instruction for this is available in the Infobak under www. keb.de in section "Downloads". Description of the Interface Voltage supply Figure 3.1...
Analog Input ±10V at Channel 2 Channel 2 3.3.1 Specifications Terminal strip 4-pole Interface type Analog input Input voltage ±10 Vdc Input resistance 60 kΩ Scan time 1 ms 3.3.2 Description of X3B Figure 3.3.2 Socket X3B Attention ! Plug connector only when COMBIVERT and supply voltage are switched off ! Name...
Analog Input ±10V at Channel 2 4.1.2 Parameter adjustments for speed-/frequency setting Display parameter Parameter Description ru.31 AN3 pre amplifier display Percentage display of the input value of the analog option ru.32 AN3 post amplifier display Percentage display of the analog channel after amplification and limitation Parameters for the adjustment of the analog channel Parameter Description An.20...
Analog Input ±10V at Channel 2 4.1.3 Further adjustments Further adjustments and application possibilities can be taken from the appropriate appli- cation manual. GB -9...