Rated Motor Speed; Rated Motor Current; Rated Motor Frequency - KEB COMBIVERT F5 Instruction Manual

Elevator drive
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Parameter Description - Motor Data
Rated motor speed
Rated motor current
Rated motor frequency
82
Unit:
PM
Value range :
Default setting:
Adjustment value:
plate
For permanent magnet synchronous motors there is no slip.
Therefore the value entered must be exactly the synchronous
rotational speed based on the rated frequency as noted below.
With this there is no further adjustment necessary. Do not round
this value off to the nearest whole number. With this there is no
further adjustment necessary.
LF.13 x 120
LF.11 =
motor poles
Enter the motor nameplate rated current (FLA).
IM
Unit:
Value range:
PM
Default setting:
Adjustment value:
plate
Enter the exact rated frequency of the motor.
IM
Unit:
Value range:
PM
Factory setting :
Adjustment value:
rpm
10.0....6000.0 or 500.0
(based on configuration mode)
1165.0 or 150.0
(based on configuration mode)
in accordance with the motor name
ampere
1.0...1.1 x Inverter rated current
8.0 A
in accordance with the motor name
hertz
4.0...100.0 Hz
60.0 Hz
in accordance with the motor name plate