Initial Start Up
5. Initial Start-up
5.1 Selecting The Configuration
i
5.2 Loading The Configuration
54
Before trying to operate the drive it is necessary to establish the correct mode
of operation. The F5 drive is capable of driving different types of motors both
open and closed loop. Therefore prior to operation, the type of motor and
mode of operation (open or closed loop) must be established.
Note: In most cases the elevator control manufacturer will make the
adjustment of the configuration and control mode, sections 6.1,6.2,6.3,
and therefore it is not necessary to make these adjustments in the field. In
this case simply verify parameter LF.4 matches the required configuration
number listed below.
The available motors and modes or configurations are listed below. From this
list it is possible to select the correct configuration setting of the Drive.
Motor
Type
Induction Geared
Induction Gearless
PM Synchronous Geared
PM Synchronous Gearless
With the configuration code noted, go to parameter US.10 on the keypad of the
drive and press "Function." Select the configuration code indicated and press
"Enter."
Once the configuration is selected, it is now necessary to load the configuration
file. This adjusts the drive for the correct motor type and establishes the correct
internal settings.
To load the configuration go to parameter US.04, set the display to LoAd and
press enter. The display will show Pro9 and the configuration file will be loaded.
The display will confirm whether the load was successful. If the display ultimately
changes to parameter LF. and shows noP, the load was successful. If the
file is not completely loaded, the display will show bdPAS for bad operation and
will remain at parameter US.4. In this case power cycle the drive and try to load
the configuration again. Make sure that no inputs are active while trying to load
the configuration. LF.82 should read 0. If still unsuccessful there may be an
incompatibility between the operator and the drive. Contact the manufacturer
for further assistance.
After loading, the configuration can be verified through parameter LF.4. The
same configuration code as that selected in US.10 will be displayed in LF.4.
Also after a successful load US.4 will display PASS.
Open
Closed
Configuration
Loop
Loop
Display Code
-
x
-
x
-
x
-
x
ICLSd
I9LSS
PCLSd
P9LSS