Electrical Power Network Specification - ABB ACH580-01 Hardware Manual

Table of Contents

Advertisement

286 Technical data
Frame
Cable entries
size
Holes
pcs
3-phase U 1 = 440...480 V, P n at U n = 480 V, 60 Hz
R1
3
R2
3
R3
3
R4
4
R5
3
R6
4
R7
4
R8
4
R9
4
3-phase U 1 = 525...600 V, P n at U n = 575 V, 60 Hz
R2
3
R3
3
R5
3
R7
4
R8
4
R9
4

Electrical power network specification

Voltage (U 1 )
Max cable
+24V, DCOM, DGND, EXT.
size
24V terminals
Wire size
in
AWG
0.67
24...14
0.67
24...14
0.67
24...14
0.67
24...14
0.67
24...14
0.67
26...14
0.67
26...14
0.67
26...14
0.67
26...14
0.67
24...14
0.67
24...14
0.67
24...14
0.67
26...14
0.67
26...14
0.67
26...14
ACH580-01-xxxx-2 drives: Input voltage range 3~ 208...240
V AC +10%.... -15%.
IEC: This is indicated in the type designation label as typical
input voltage levels 3~ 230 V AC.
North America: This is indicated in the type designation label
as typical input voltage levels 1~ 208/230 V AC and 3~
208/230 V AC.
ACH580-01-xxxx-4 drives: Input voltage range 3~ 380...480
V AC +10%...-15%.
This is indicated in the type designation label as typical input
voltage levels 3~ 400/480 V AC.
ACH580-01-xxxx-6 drives: Input voltage range 3~ 525...600
V AC +10%...-15%.
This is indicated in the type designation label as typical input
voltage level 3~ 600 V AC.
Control cable entries and terminal sizes
T
lbf·ft
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
DI, AI/O, AGND, RO, STO
terminals
Wire size
T
AWG
lbf·ft
26...16
0.4
26...16
0.4
26...16
0.4
26...16
0.4
26...16
0.4
26...14
0.4
26...14
0.4
26...14
0.4
26...14
0.4
26...16
0.4
26...16
0.4
26...16
0.4
26...16
0.4
26...16
0.4
26...16
0.4

Advertisement

Table of Contents
loading

Table of Contents