2. Hardware description

Power connections and control interfaces

Screen
Analog input 1
0...10 V
Reference voltage
+10 V DC, max. 10 mA
Analog input 2
Aux. voltage output
+24 V DC, max. 200 mA
PROGRAMMABLE
DIGITAL INPUTS
DI5 can also be used
as a frequency input
Modbus RTU
(RS-485)
FlashDrop
3-phase power
supply,
200...480 V AC
1
SCR
2
AI1
3
GND
4
+10V
5
AI2
6
GND
9
+24 V
10
GND
11
DCOM
12
DI1
13
DI2
14
DI3
15
DI4
16
DI5
23
SHIELD
24
J701
B
25
A
26
GND_A
6
PE
L1
U1
L2
V2
L3
W1
8
S1
AO 7
GND 8
mA
V
ROCOM
17
RONC
18
RONO
19
DOSRC
20
DOOUT
21
DOGND
22
EMC
VAR
U2
V2
W2
Hardware description 7
Control panel
(RJ-45)
Modbus RTU
(RS-232)
Analog output
0...20 mA
PROGRAMMABLE RELAY
AND DIGITAL OUTPUTS
Relay output
250 V AC / 30 V DC / 6 A
Digital/frequency output,
PNP transistor type
30 V DC, max. 100 mA
6
Output relay
module MREL-01
EMC filter grounding screw
Varistor grounding screw
M
AC motor
3 ~

Advertisement

Table of Contents
loading