Options Set Up Group - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Configuration

4.12 Options Set Up Group

Introduction
The Options group lets you configure the remote mode switch (Digital Inputs) to a
specific contact closure response, or configure the Auxiliary Output to be a specific
selection with desired scaling.
Function Prompts
Table 4-11 Options Group (Numeric Code 900) Function Prompts
Prompt
English
Numeric
Code
AUXOUT
901
0 PCT
902
100 PCT
903
DIG IN
904
DI COM
905
38
Description
Numeric
Auxiliary Output
Auxiliary Output
Low Scaling Factor
Auxiliary Output
High Scaling
Factor
Digital Input
Digital Input
Combinations
UDC2300 Controller Product Manual
Selection or Range of Setting
English
Code
0
DIS
Disabled
1
IN1
Input 1
2
IN2
Input 2
3
PROC
Process Variable
4
DEV
Deviation
5
OUT
Output
6
SP
Setpoint
7
LSP1
Local Setpoint 1
Value in Engineering Units
Value in Engineering Units
0
None
1
MAN
To Manual
2
LSP
To Local SP 1
3
SP2
To Local SP 2
4
DIR
Direct Control
5
HOLD
Hold SPP/SP Ramp
6
PID2
PID Set 2
7
RUN
Start a stopped
SPP/SP Ramp
8
Begn
SPP Reset
9
NO I
Inhibit Integral
10
MNFS
Manual, Failsafe
Output
11
LOCK
Keyboard Disable
12
TIMR
Start Timer
13
TUNE
Start Tune
14
INIT
Init SP to PV
RSP
Remote SP
15
16
MNLT
Latching Manual
17
TRAK
Output tracks Input 2
0
DIS
Disable
1
+ PD2
PID Set 2
2
+DIR
Direct
3
+SP2
Set Point 2
4
+SP1
Set Point 1
5
+RUN
Start SPP
Factory
Reference
Setting
Guide
Page
DIS
122
0
119
100
119
NONE
131
DIS
131
12/00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents