Communications Set Up Group - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

4.13 Communications Set Up Group

Introduction
The Communications group lets you configure the controller to be connected to a host
computer via RS422/486 or Modbus® protocol.
Function Prompts
Table 4-12 Communications Group (Numeric Code 1000)
Prompt
English
Numeric
Code
COMSTA
1001
ComADD
1002
SDENAB
1003
SHDTIM
1004
PARITY
1005
BAUD
1006
TX_DLY
1007
WS_FLT
1008
12/00
Description
Numeric
Code
Communications
State
Station Address
Disable/Enable
Shed function
Shed Time
Parity
Baud Rate
Response Delay
Word/Byte Order
for floating point
communications
data
0
1
2
3
UDC2300 Controller Product Manual
Selection or Range of Setting
English
0
DIS
Disable
1
R422
RS-422/485
2
MODB
Modbus
1 to 99
DIS
Disable
0
ENAB
Enable
1
Note: If Control Algorithm is 3
Position Step Control then this
must be enabled.
0 to 255 Sample Periods
0
Odd
1
Even
0
2400 Baud
1
4800 Baud
2
9600 Baud
3
19200 Baud
1 to 500 milliseconds
Byte
Contents
0
seeeeeee
1
emmmmmmm
2
mmmmmmmm
3
mmmmmmmm
Choice
Byte Order
FP_B
0123
FPBB
1032
FP_L
3210
FPLB
2301
Configuration
Factory
Reference
Setting
Guide
Page
DIS
0
ENAB
0
Odd
2400
1
FP_B
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents