Figure 2-10 Solid State Relay Output - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Supply
1
2
See Figure 2-15 for Alarm and Duplex Output Connections.
See Table 2-3 and Table 2-4 for Control and Alarm Relay Contact information.
Customer Supplied External
Electromechanical Relay
0-24 Vdc
1
1
CAUTION
See Figure 2-15 for Alarm and Duplex Output Connections.
See Tables 2-3 and 2-4 for Control and Alarm Relay Contact information
12/00
AC
2
Load
Power
Control Relay #1
Dummy Resistor
If the load current is less than the minimum rated value of 20 mA,
there may be a residual voltage across both ends of the load even
if the relay is turned off. Use a dummy resistor as shown to
counteract this. The total current through the resistor and the load
current must exceed 20 mA.
Solid State relay is rated at 1 Amp at 25°C, linearly derated to 0.5
Amp at 55°C. Customer should size fuse accordingly.

Figure 2-10 Solid State Relay Output

OUT1 OUT2/ALM2
9 –
5–
4+
10+
+
Open collector outputs are internally powered at 24 Vdc.
Connecting an external supply will damage the controller.
External relays should be fused between power and relay load.
Figure 2-11 Open Collector Relay Output
UDC2300 Controller Product Manual
1 amp Fast Blo
OUT1
5
4
Load
1
Customer Supplied External
Solid State Relay
OUT1
1
5 –
4+
+
0-24 Vdc
Installation
OUT2/ALM2
9
10
24860
OUT2/ALM2
9 –
10+
24861R
.
15