Table 4-10 CONTRL Group (Numeric Code 800) Function Prompts, continued
Prompt
English
Numeric
Code
OUT Hi
811
OUT Lo
812
D BAND
813
HYST
814
FAILSF
815
816
FSMODE
817
PBorGN
818
MINRPM
819
12/00
Description
Numeric
High Output Limit
Low Output Limit
Deadband
Hysteresis (Output
Relay Only)
Failsafe Output
Value
Failsafe Mode
Proportional Band
Units
Reset Units
UDC2300 Controller Product Manual
Selection or Range of Setting
English
Code
-5 to 105 % of Output
(Current)
0.0 to 100.0 % of Output
(Relay)
-5 to 105 % of Output
(Current)
0.0 to 100.0 % of Output
(Relay)
-5 to 25.0 % (Time Duplex)
0.5 to 5.0 % (3 position
step)
0.0 to 100.0 % of PV
0 to 100 %
For 3 Position Step
0
0 (Closed position)
1
100 (Open position)
0
No L (Mode does not clear
once unit goes to FS
Output)
1
LACH (Unit goes to manual
and FS output)
0
GAIN
1
PB
0
MIN
1
RPM
Configuration
Factory
Reference
Setting
Guide
Page
100
143
0
143
2.0
130
0.5
135
0.0
134
NO_L
135
GAIN
145
MIN
142
37