Honeywell UDC2300 Product Manual page 165

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

12.2.96
SP SEL
This prompt is part of the Tuning Set up group.
This selection allows you to disable/enable the Setpoint Select function.
"LOCK" must be set to "NONE".
Selections
DIS
Disables the Setpoint Select Function.
ENAB
Enables the Setpoint Select Function.
12.2.97
SP TRK
This prompt is part of the Control Set up group.
The local setpoint can be configured to track either PV or RSP as listed below.
ATTENTION
For selections other than NONE, LSP is stored in nonvolatile memory only when there is a mode change;
i.e., when switching from RSP to LSP or from Manual to Automatic. If power is lost, then the current LSP
value is also lost.
Selections
NONE
NO TRACKING—If local setpoint tracking is not configured, the LSP will
not be altered when transfer from RSP to LSP is made.
PV
PROCESS VARIABLE—Local setpoint tracks the PV when in manual.
RSP
REMOTE SETPOINT—Local setpoint tracks remote setpoint when in
automatic. When the controller transfers out of remote setpoint, the last
value of the remote setpoint (RSP) is inserted into the local setpoint.
12.2.98
START
This prompt is part of the Timer Set up group. This selection allows you to select
whether the Timer starts with the keyboard
Selections
KEY
Starts with
AL2
Starts on Alarm 2.
12.2.99
STATE
This prompt is part of the Setpoint Ramp/Program Set up group.
The program state selection determines the program state after completion.
Selections
DIS
Program disabled at program end.
HOLD
Program held at program end.
12/00
(SETPOINT SELECT FUNCTION LOCKOUT)
Definitions
(SETPOINT TRACKING)
Definitions
(TIMER START SELECTION)
RUN/HOLD
Definitions
key.
RUN/HOLD
(PROGRAM STATE AT PROGRAM END)
Definitions
UDC2300 Controller Product Manual
Function Parameter Reference Guide
key or Alarm 2.
155