Honeywell UDC2300 Product Manual page 130

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Function Parameter Reference Guide
12.2.4
A TUNE
This prompt is part of the Tuning Set up group.
This selection allows you to disable the
Selections
DIS
Disable the
ENAB
Enables the
12.2.5
ACTION
This prompt is part of the Control Set up group.
This selection allows you to select the direction you want the controller output to go when
the process variable increases.
Selections
DIR
DIRECT ACTING CONTROL—The controller's output increases as the
process variable increases.
REV
REVERSE ACTING CONTROL—The controller's output decreases as
the process variable increases.
12.2.6
ALARM1
This prompt is part of the Alarms Set up group.
Each alarm output can be configured to be Latching or Non-latching.
ATTENTION
When configured for latching, the alarm will stay on, after the alarm condition ends, until the
RUN/HOLD key is pressed.
Selections
NO L
Non-Latching
LACH
Latching
120
(AUTOTUNE KEY LOCKOUT)
AUTOTUNE
Definitions
key
AUTOTUNE
key
AUTOTUNE
(CONTROL OUTPUT DIRECTION)
Definitions
(LATCHING ALARM FOR OUTPUT)
Definitions
UDC2300 Controller Product Manual
key. "LOCK" must be set to "None".
12/00