Troubleshooting/Service
Lower
Display
Two consecutive failures of input 2
IN2_FL
integration. i.e., cannot make analog to
digital conversion.
CNFERR
• PV low limit is > PV high limit
• SP low limit is > SP high limit
• Output low limit > Output high limit
PV out of range.
PV LIM
PV = INP1 x RATIO1+ INP1 BIAS
The result of the formula shown below
RV LIM
is beyond the range of the remote
variable.
RV = INP2 X RATIO + BIAS
Setpoint Program start segment
SEGERR
number is less than ending segment
number.
106
Reason for Failure
UDC2300 Controller Product Manual
How to Correct the Problem
Same as IN1FL above.
1. Check the configuration for each item and
reconfigure if necessary.
1. Make sure the input signal is correct.
2. Make sure the Ratio and Bias settings are
correct.
3. Recheck the calibration. Use Bias of 0.0
1. Make sure the input signal is correct.
2. Make sure the Ratio2 and Bias2 settings are
correct.
3. Recheck the calibration. Use a Ratio2 of 1.0
and a Bias2 of 0.0.
1. Check SP Program configuration, subsection
4.6 Set up Group SPPROG function prompts
"STRSEG" and "ENDSEG".