Input Set Up Group

Table 10 lists the parameters and selections available when the SET INPUT group is selected.
On the keypad and local display:
Press the SET UP key to enter the Input Set Up group.
Press the FUNCTION key to scroll through the prompts listed in the set up group.
Press the
Actuator Lower
Display
Prompt
IN TYP
Note: If input
type from model
selection guide
is:
0/4-20mA, 0/1-
5Vdc, 0-10Vdc
IN TYP
INP HI
INP LO
Revision 6
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
7/07
or
keys to view selections or change range settings.

Table 10 Input Set Up Group Parameters

Selections or
Range of Setting
4-20
0-20
1-5V
0-5V
0-10
R_SP
S_90
10.0 to 100
default = 100
0.0 to 90.0
default = 0.0
Parameter Definition/PDA HercuLink Prompt
INPUT ACTUATION TYPE— This selection specifies the
signal type and range you are going to use for the actuator
input. Be sure that the values configured for the high and low
range, alarm setpoint, etc. are within the measuring range
for the selected signal range.
4 to 20 mA
0 to 20 mA
1 to 5 Volts dc
0 to 5 Volts dc
0 to 10 Volts dc
Remote Setpoint (via communications)
NOTE: Changing the Input Actuation Type will restore the
actuator calibration to its factory values.
Series 90 – 0 to 135 ohms.
Note: If input type from model selection guide is: Series 90
control
INPUT HIGH RANGE VALUE in % is displayed.
NOTE: When Input Type (R_SP or S_90) is selected, Input
Hi is not configurable.
INPUT LOW RANGE VALUE in % is displayed.
NOTE: When Input Type (R_SP or S_90) is selected, Input
Hi is not configurable.
Set Up and Calibration Procedures
Input Set Up Group
39